BACKUP POWER & AMF SIZING
Diesel Generator (DG Set) Sizing Calculator.
Size commercial and industrial emergency diesel generators (kVA) by evaluating essential running load, largest motor starting inrush transients, fuel consumption at 75% load, and AMF changeover panel ratings.
Step 1: Emergency Power Audit
Critical Backup Load Parameters
Total Essential Running Load
kW
Single Largest Motor on Backup System
HP
DOL causes 6× inrush current; Star-Delta reduces surge to 3×; VFD minimizes generator sizing.
Generator Reserve Margin20%
Recommended DG Set Rating
125kVA
3-Phase 415V Diesel Generator with CPCB-IV+ Acoustic EnclosureOperational Loading65%Optimal DG longevity zone (60%–80%)
Rated Current174 Aat 415V 3-Phase
Fuel Consumption~27.5 L/hrat 75% load
AMF Breaker218 A4-Pole Incomer
Mains Failure Changeover:< 15 Seconds (Auto-Start AMF)
AMF Synchronization & Panel Engineering
Automatic Mains Failure (AMF) Panel: Microprocessor-based auto-start controller monitoring 3-phase KSEB grid voltage, frequency, and phase sequence.
Interlocking Protection: 4-Pole motorized changeover switch with electrical and mechanical interlocks to prevent utility backfeeding into the grid.